The AFDD Arc Fault Detection Device is a critical safety solution engineered to mitigate electrical fire risks in residential, commercial, and industrial environments. By combining arc fault detection, residual current protection, and overload/short circuit safeguards, it offers comprehensive defense against common electrical hazards. With four adjustable sensitivity modes, it adapts to diverse settings—from homes to factories—while intuitive indicators and a test button ensure ease of monitoring and maintenance. Its modular DIN rail design simplifies installation, making it an essential upgrade for modern electrical systems.
Contact Us

Arc fault detection (series, parallel, ground arcs)
Residual current protection (IΔn = 0.03A)
Overload (long/short delay) and instantaneous trip protection.
1 flash: Interference-resistant mode (low sensitivity, for high-interference environments like industrial machinery).
2 flashes: Strict mode (general factories, complex power systems).
3 flashes: Normal mode (residential, offices, dormitories).
4 flashes: Sensitive mode (long lines with minimal grid interference).
Reset Button: Manual reset after arc interruption.
Indicator Lights: Green (normal operation), Red (fault alarm, flashing post-trip).
Test Button: Short-press to simulate arc trips for functionality checks.

| Item | Parameter | Data |
|
Electricalfeatures |
Rated voltage Ue (V) | 230V~ |
| Rated current In (A) | 6A,10A,16A,20A,25A, 32A,40A,50A,63A | |
| Rated sensitivity I ∆ n(A) | 0.03A | |
| Poles | 2P+N、2P | |
| Wave form of the earth leakage sensed | AC | |
| Thermo-magnetic release characteristic | C(5-10In) | |
| Rated short circuit capacity Icn (A) | 6000 | |
| Rated residual making and breaking capacity I ∆ m (A) | 500A(In ≤ 50A),630A(In ≤ 63A) | |
| Rated insulation voltage Ui (V) | 500V | |
| Rated impulse withstand voltage Uimp (V) | 4000V | |
| Pollution degree | 2 | |
|
Mechanicalfeatures |
Electrical life | 10000 |
| Mechanical life | 20000 | |
| Protection degree | IP20 | |
| Ambient temperature (℃ ) | -25~+40 | |
| Storage temperature (℃ ) | -25~+70 | |
| Installation | Tightening torque (N.m) | 2 |
| Terminal size for cable (mm) | 16 | |
| Installation category | Ⅱ |
| Model | In(A) | I ∆ n | Time limit for tripping or not tripping | |||
| I ∆ n | 2I ∆ n | 5I ∆ n | ||||
| AFDD-63 |
6A,10A,16A, 20A,25A,32A, 40A,50A,63A, |
>0.03 | 0.03 | 0.15 | Maximumtripping time | |
| 0.03 | 0.03 | 0.15 | ||||
| <0.03 | 0.03 | 0.15 | 0.04 | |||
| Arc current of test(the effective value) | 3A | 6A | 13A | 20A | 40A | 63A |
| Maximum tripping time | 1s | 0.5s | 0.25s | 0.15s | 0.12s | 0.12s |
| Arc current of test(the effective value) | 75A | 100A | 150A | 200A | 300A | 500A |
| N | 12 | 10 | 8 | 8 | 8 | 8 |
| Type | In(A) | Tripping time | Expected result |
| B,C,D | 1.13In | t ≤ 1h(In ≤ 63A) | Not tripping |
| 1.13In | t ≤ 2h(In>63A) | ||
| B,C,D | 1.45In | t<1h(In ≤ 63A) | Tripping |
| 1.45In | t<2h(In>63A) | ||
| B,C,D | 2.55In | 1s<t<60s(In ≤ 32A) | Tripping |
| 2.55In | 1s<t<120s(In>32A) |
| Type | In(A) | Tripping time | Expected result |
| B,C,D | B | t ≤ 0.1s | Not tripping |
| C | t ≤ 0.1s | ||
| B,C,D | D | t ≤ 0.1s | |
| B | t<0.1s | Tripping | |
| B,C,D | C | t<0.1s | |
| D | t<0.1s |


| Fault cause | Fault analysis | Troubleshooting |
Table 6 |
|
| Refusal to operate | The AFDD circuit breakeris not connected to the
neutral wire, causing refusal to operate |
The AFDD circuit breaker is onlyconnected to the phase wire on the
power side and the neutral wire is not connected. |
Connect the neutral wire on the powerside. | |
| False tripping | The AFDD circuit breaker trips due to a short circuit | The line (L) and neutral (N) wiresat the incoming and outgoing
terminals of the AFDD circuit breaker are crossed |
Strictly follow the wiring diagram andthe product markings to correctly
connect the circuit. |
|