For solar installers, system integrators, and facility managers, protecting DC circuits in photovoltaic systems is a daily priority. Overloads, short circuits, and reverse currents can disrupt energy production, damage expensive components like inverters and modules, or even pose safety risks. Standard AC breakers fall short here—DC faults are harder to interrupt, and solar systems demand precision protection tailored to their unique voltage ranges and load patterns.
Contact Us
| Parameter | Specifications |
|---|---|
| Rated Current | 1A–63A (1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A) |
| Poles | 1P, 2P, 3P, 4P (flexible for system design) |
| Max Voltage | DC1200V (covers most solar applications) |
| Breaking Capacity | 6kA (standard) or 10kA (H-version for high-fault systems) |
| Mechanical Life | 20,000 cycles (reduces replacement frequency) |
| Electrical Life | 1,500 cycles (sustained performance under load) |
Solar equipment operates in extremes—baking in +40°C heat during the day, freezing at -25°C at night. The YCB8s-63PVn is tested to perform reliably in these conditions, with:
Consider a 2MW commercial solar array in Texas. The team faced recurring issues with inverters tripping during morning startup due to inrush currents. After switching to YCB8s-63PVn 2P 32A (K Curve) breakers:
“We needed a breaker that ‘understood’ solar—one that protected without getting in the way,” said the project’s electrical lead. “YCB8s delivered exactly that.”
| Number of poles | 1P | 2P | 3P | 4P |
| Rated operating voltage Ue (V) | DC300 | DC600 | DC900 | DC1200 |
| Rated insulation voltage Ui(V) | DC300 | DC600 | DC900 | DC1200 |
| Rated impulse withstand voltage Uimp (KV) | 6 | |||
| Rated frame current (A) | 63 | |||
| Rated current In(A) | 1,2,3,4,6,10,16,20,25,32,40,50,63 | |||
| Ultimate short-circuit breaking capacity Icu (KA) | Default:6;H:10 | |||
| Instantaneous tripping characteristic | B,C,K | |||
| Service life (times) | Mechanical 20000,electrical life 1500 | |||
| Protection degree | IP20 | |||
| Environmental temperature for use | -25℃~+40℃ | |||
| Altitude | ≤2000m | |||
| Wiring ability(mm²) | 25 | |||
| Connection | both upper andlower incoming lines are acceptable | |||
| Use Category | A | |||
| Standard | IEC60947-2 | |||
We know your priority is delivering systems that work—on time, within budget, and with minimal headaches. The YCB8s-63PVn isn’t flashy, but it’s:
| Rated current(A) | Overload tripping characteristics | Instantaneous tripping characteristics(A) |
|
| 1.05In agreed non tripping time H(cold state) | 1.30ln agreed tripping time H (hot state) | ||
| In≤63 | 1 | 1 | B(4In±20%) C(8ln±20%) K(10In±20%) |
| In>63 | 2 | 2 | |
| Rated current(A) Ambient temperature corresponding to rated current(A) | ||||||||||||
| In(A) | -25℃ | -20℃ | -10℃ | 0℃ | 10℃ | 20℃ | 30℃ | 35℃ | 40℃ | 50℃ | 60℃ | 75℃ |
| 6A | 10.12 | 9.77 | 9.03 | 8.26 | 7.49 | 6.75 | 6 | 5.59 | 5.19 | 4.75 | 4.62 | / |
| 10A | 17.41 | 16.75 | 15.41 | 14.04 | 12.71 | 11.35 | 10 | 9.09 | 8.21 | 7.9 | 8.7 | 7.86 |
| 16A | 21.72 | 21.15 | 20.15 | 19.12 | 18.08 | 17.04 | 16 | 15.49 | 15.1 | 14.38 | 13.52 | 12.75 |
| 20A | 25.86 | 25.79 | 24.61 | 23.47 | 22.32 | 21.16 | 20 | 19.43 | 18.83 | 18.58 | 17.1 | 16.3 |
| 25A | 32.41 | 31.74 | 30.37 | 28.98 | 27.69 | 26.35 | 25 | 24.33 | 23.65 | 23.3 | 24.7 | 23.8 |
| 32A | 44.83 | 43.62 | 41.29 | 38.96 | 36.67 | 34.33 | 32 | 30.83 | 29.67 | 30.7 | 30.8 | 30 |
| 40A | 50.34 | 49.35 | 47.51 | 45.62 | 43.73 | 41.87 | 40 | 39.04 | 38.11 | 38.6 | 36.2 | 35.8 |
| 50A | 63.79 | 62.48 | 59.99 | 57.48 | 54.98 | 52.5 | 50 | 48.76 | 47.48 | 47.1 | 47.5 | 46 |
| 63A | 80 | 78.46 | 75.38 | 72.28 | 69.17 | 66.09 | 63 | 61.46 | 59.93 | 55.6 | 53.8 | 52.4 |
| Model | YCB8s-63 OF | YCB8s-63 SD | YCB8s-63 MX | |
| Number of contacts | 1NO+1NC | 1NO+1NC | / | |
| Control voltage (VAC) | 110-415 48 12-24 |
|||
| Control voltage(V DC) | 110-415 48 12-24 |
|||
| Working current of contact | AC-12 Ue/le:AC415/3A DC-12 Ue/le:DC125/2A |
/ | ||
| Shunt control voltage | Ue/le: AC:220-415/ 0.5A AC/DC:24-48/3 |
|||
| Width(mm) | 9 | 9 | 18 | |
| Applicable Environmental Conditions and Installation | ||||
| Storage temperature(C) | -40℃~+70℃ | |||
| Storage humidity | the relative humidity does not exceed 95%when at+25℃ | |||
| Protection degree | Level 2 | |||
| Protection degree | IP20 | |||
| Installation environment | Places without significant vibration and impact | |||
| Installation category | Category Ⅱ,Category Ⅲ | |||
| Installation method | TH35-7.5/DIN35 rail installation | |||
| Maximum wiring capacity | 2.5mm² | |||
| Terminal torque | 1N ·m | |||