Product Overview
Product Details
Data Download
Related Products
Voltage and current display relay is a microprocessor-based voltage monitoring device for sinale-phase AC networks to protect electrical equipment from surge voltage. The device analyzes the main voltage and displays its curent value on a digital indicator. Load is switched by electro magnetic relay. The user can set the current voltage value and delay time through the button.The value is stored in non-volatile memory. Aluminum wires and copper wires can be used for connection.
Contact Us
Voltage and current display relay is a microprocessor-based voltage monitoring device for sinale-phase AC networks to protect electrical equipment from surge voltage. The device analyzes the main voltage and displays its curent value on a digital indicator. Load is switched by electro magnetic relay. The user can set the current voltage value and delay time through the button.The value is stored in non-volatile memory. Aluminum wires and copper wires can be used for connection.
Voltage and current display relay used in administrative, industrial and residential buildings and has the function of protecting single-phase lines:
• Undervoltage protection;
• Overvoltage protection;
• Working under voltmeter mode;
• Overcurrent proteciton.
YC 7 VA N - 1 63A 230V
| Company code |
Design Number |
Functional Type | New style | Phase Number Type |
Rated Current |
Voltage |
| YC | 7 | VA | N | 1 | 63A | 230V |
| / | / | V:Voltage A:Current VA:Voltage and Current KWH:Voltage,Current, and Kilowatt-hours |
/ | 1 Single-phase(de- fault without notes) 3 Three-phase |
40A:40A 63A:63A 80A:80A |
Single-phase:230V |
1. Ambient temperature: -20°C~+55°C
2. Relative humidity: ≤20% at 40°C; ≤90% at 20°C
3. Altitude: ≤2000m
4. Environmental conditions: no harmful gases and vapors, no conductive or explosive dust, no severe mechanical vibration.
| Function | Technical Parameter | Function | Technical Parameter |
| Input voltage | AC 140-300V | Power-on delay time | 1-500s default 10s |
| Over-voltageprotection value | 130-300V default 275V | Over-voltage recovery value | 225-295V default 275V |
| Under-voltageprotection value | 80-210V default 175V | Under-voltage recovery value | 145-215V default 175V |
| Over-currentprotection value | 40A:1-40A default 40A | Powe rconsumption | 2W |
| 63A:1-63A default63A | Boundary dimendion | 86×38×68mm | |
| Recovery delaytime | 1-500s default 30s | Action time | 0.1-30s default 1s |
| Continuous overcurrent faults times | 1-20 times default OFF | Electrical and mechanical life | 2100000cycles |
| Wiring | Over-entering down-out |
1. In caseofover-voltagefault, under-valtagefault orover-current tault insingleghaseline, the product canpower line over a time delay after voltageor current of the lineis recovered to normal condition.
2. In case of transient over voltageinline, the product canprotect the equipmant from false aperation.
3. In case that theline subjects to unstable Voltage connectionand other fault, the product willdisconnec theline.
4. When fault vollage of thelinereaches thepeak, the product it self will not bedamaged.
YC7VAN 63A 230V 50 pieces