Product Overview
Product Details
Data Download
Related Products
The YCB7NLE-125 RCBO Electronic is a high-performance residual current circuit breaker designed for final distribution applications. It offers rated currents of 63A, 80A, and 100A, with exceptional features including high flame retardancy, temperature resistance, and impact resistance.
Boasting a short-circuit breaking capacity of 6000A, it ensures reliable protection against overloads and short circuits for cables and lines, while also providing personnel and fire protection
Contact Us
1. Personnel and fire protection
2. Cable and line protection against overload and short-circuits
1. IΔn ≤ 30 mA: additional protection in the case of direct contact.
2. lΔn ≤300 mA: preventative fire protection in the case of ground fault currents.
3. lΔn class - Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.
| Type | Tripping time | I△n(A) | Expected result | Note | |||||
| IΔn | 2I△n | 5I△n | 6I△n | ||||||
| General | 63,80, 100,125 |
≥0.03 | 0.1 | 0.07 | 0.04 | 0.04 | Minimum time for tripping | ||
| Time delay | Time limit for not tripping |
0.06s | ≥0.03 | 0.3 | 0.2 | 0.15 | 0.15 | Minimum time for tripping | |
| ≥0.03 | 0.13 | 0.06 | 0.05 | 0.04 | Minimum time for not tripping | ||||
| 0.1s | ≥0.03 | 0.6 | 0.4 | 0.3 | 0.2 | Minimum time for tripping | |||
| ≥0.03 | 0.23 | 0.1 | 0.06 | 0.05 | Vinimum time for not tripping | ||||
| Type | Test current | Tripping time | Expected result |
| C,D | 1.05In | t≤1h(In≤63A),t≤2h(In>63A) | Not tripping |
| C,D | 1.3In | t≤1h(IIn≤63A),t≤2h(In>63A) | Tripping |
| C,D | 2.55In | 1s<t<120s | Tripping |
| C | 8lnx80% | t≤0.2s | Not tripping |
| D | 12Inx80% | t≤0.2s | Not tripping |
| C | 8lnx120% | t≤0.2s | Tripping |
| D | 12Inx120% | t≤0.2s | Tripping |
| Type | Standard | IEC/EN 60947-2 | |
| Electrical features |
Type(wave form of the earth leakage sensed) | AC | |
| Thermo-magnetic release characteristic | (C)li=8ln,(D)li=12In | ||
| Rated current In | A | 63,80,100,125 | |
| Poles | 1P+N,2P,3P,3P+N,4P | ||
| Rated voltage Ue | V | 230/400 | |
| Rated sensitivity I△n | A | 0.03,0.1,0.3 | |
| Rated short-circuit capacity Icn | A | 6000 | |
| Break time under △n | S | ≤0.1 | |
| Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
| Dielectric TEST voltage at ind.Freq.for 1min | kV | 1.89 | |
| Insulation voltage Ui | V | 500 | |
| Pollution degree | 3 | ||
| Electrical life | 1500 | ||
| Mechanical features |
Mechanical life | 8500 | |
| Contact position indicator | Yes | ||
| Protection degree | IP20 | ||
| Ambient temperature (with daily average≤35℃) | ℃ | -5~+40 | |
| Storage temperature | ℃ | -25~+70 | |
| Installation | Terminal connection type | Cable/Pin-type busbar | |
| Terminal size top/bottom for cable | mm² | 16~50 | |
| AWG | 6-1/0 | ||
| Terminal size top/bottom for busbar | mm² | 16~35 | |
| AWG | 6-2 | ||
| Tightening torque | N*m | 3.5 | |
| In-lbs | 31 | ||
| Mounting | On DIN rail EN 60715(35mm)by means of fast clip | ||
| Connection | From top or bottom |