YCB9RL-100 RCCB Electromagnetic | CNC Electric
YCB9RL-100 RCCB Electromagnetic
YCB9RL-100 RCCB Electromagnetic
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

YCB9RL-100 RCCB Electromagnetic
Picture
Video
  • YCB9RL-100 RCCB Electromagnetic
  • YCB9RL-100 RCCB Electromagnetic
  • YCB9RL-100 RCCB Electromagnetic
  • YCB9RL-100 RCCB Electromagnetic
  • YCB9RL-100 RCCB Electromagnetic
  • YCB9RL-100 RCCB Electromagnetic
  • YCB9RL-100 RCCB Electromagnetic
  • YCB9RL-100 RCCB Electromagnetic
YCB9RL-100 RCCB Electromagnetic Featured Image

YCB9RL-100 RCCB Electromagnetic

General
1.Protection against the effects of sinusoidal alternating earth fault currents
2.Protection against indirect contacts and additional protection against direct contacts
3.Protection against fire hazard caused byinsulation faults
4.Controlling and Switching
5.Used in residential building,non-residential building,energysources,industryand infrastructure

Contact Us

Product Details

YCB9RL-100-product-description1

General

1. Protection against the effects of sinusoidal alternating earth fault currents
2. Protection against indirect contacts and additional protection against direct contacts
3. Protection against fire hazard caused by insulation faults
4. Controlling and Switching
5. Used in residential building, non-residential building, energy sources, industry and infrastructure

Release

Type Tripping sensitivity data
AC For residual sinusoidal alternating currents 10mA,30mA For personnel,material and fire protection,as well as Tor protection against airect contact
A For residual sinusoidal alternating currents and residual pulsating direct currents 100mA For providing protection against indirect contacts
S For selectivity,with time delay 300mA For providing fire protection in case of insulation faults

Wiring Diagram

YCB9RL-100-product-description3

Specifications

Overall and Mounting Dimensions (mm)

Type Standard   IEC/EN 61008-1
Electrical
features
Leakage type   Electromagnetic type
Rated current In A 6,10,16,25,32,40,50,63,80,100
Type(wave form of the earth leakage sensed)   A,AC,AS
Poles P 1P+N,3P+N
Rated voltage Ue V 230/400
Insulation voltage Ui V 500 
Rated frequency Hz 50/60
Rated breaking capacity Inc=I△c A 600,010,000
Rated impulse withstand voltage(1.2/50)Uimp V 6000 
Dielectric test voltage at ind.Freq.for 1min kV 2.5 
Rated sensitivity I△n A 0.01,0.03,0.1,0.3
Rated residual making and breaking capacity I△m A 500(In≤40A);630(In=50A63A);1000(In=80AV100A)
Pollution degree  
Electrical life t 4000 
Mechanical
features
Mechanical life t 8000 
Protection degree   IP20
Storage temperature -25~+70
Installation Ambient temperature(with daily average≤35℃) -5~+40
Terminal connection type   Cable/Pin-type busbar/U-type busbar
Terminal size top/bottom for cable   mm² 25/35
  AWG 18-3/18-2
Terminal size top/bottom for busbar   mm² 10/16
  AWG 18-8/18-5
Tightening torque   N*m 2.5 
In-lbs 22 
Mounting   On DIN rail EN 60715(35mm)by means of fast clip device
Connection   From top and bottom