YCC19 seiesAC Contactoris suitable forusing inthe dicuitsthe rated woltage up to400V AC 50Hz or 60HLCJ19 is usedto combine with low woltage reactive powercompensators or autoff low woltageshuntcapadtor YCC19 series ACContactorhasrestraining dewiceto effectihely decrease impact caused byinnush transient ourrentwhenswitch onor overvoltagewhen switchoft
Contact Us
YCC19 contactor for capacitor switching (hereinafter called contactor) is suitable for the circuit of AC 50Hz/60Hz with rated voltage up to 690V. It is mainly used to add low voltage reactive power compensation equipment or cut off low voltage parallel capacitor. The contactor is equipped with a device to suppress the inrush current, which can effectively reduce the impact of the making inrush current on the capacitor and suppress the over-voltage when the capacitor is cut off.
Standard: IEC/EN 60947-4-1.
• Ambient temperature:-5°C~+40°C, the average during 24 hours should not exceed +35°C;
• Altitude:≤2000m;
• Atmosphere conditions: At mounting site, relative humidity not exceed 50% at the max temperature of +40°C, higher relative humidity is allowable under lower temperature. For example, RH could be 90% at +20°C, special measures should be taken for occurrence of condensation;
• Pollution degree: 3
• Installation category: III
• Installation conditions: the inclination between installation plane and vertical plane is within ±5°
• Impact and shake: the products should locate in the places where there are no obvious impact and shake.
| Model | YCC19-25 | YCC19-32 | YCC19-43 | YCC19-63 | YCC19-95 | YCC19-115 | ||
| Main circuit features | ||||||||
| Rated operating voltage(Ue) | V | 380/400 | ||||||
| Rated isolation voltage(Ui) | V | 690 | ||||||
| Rated current of controllable capacitor(In) |
AC-6b 400V | A | 17 | 29 | 36 | 43 | 72 | 87 |
| Rated capacity of controllable capacitor(Qn) |
AC-6b 230V | kVar | 6 | 9 | 10 | 15 | 22.5 | 35 |
| AC-6b 400V | kVar | 12 | 18 | 20 | 30 | 45 | 60 | |
| Rated conventional heating current(Ith) | A | 7.5 | 32 | 43 | 63 | 95 | 115 | |
| Restrained surge capacity | A | ≤35In | ≤55In | |||||
| Mechanical durability | 10⁴times | 100 | ||||||
| Electrical durability | AC-6b 400V | 10⁴times | 15 | 12 | ||||
| Operating frequency cycles/h | AC-6b 400V | times/h | 300 | 120 | ||||
| Coil features | ||||||||
| Controlled power voltage(Us) | AC50Hz | V | 110,220,380 | |||||
| Operating voltage range | operation voltage |
V | 85%~110%Us when install inclination angle is+22.5°; 70%~120%Us when install inclination angle is±5°; |
|||||
| release voltage |
V | 20%~75%Us when install inclination angle is+22.5°; 20%~65%Us when install inclination angle is±5°; |
||||||
| Auxiliary contact features | ||||||||
| Number of auxiliary contact | 1,221 | |||||||
| Rated conventional heating current(Ith) | A | 10 | ||||||
| The minimum load can be connected to | 6V×10mA | |||||||
| Model | Overall dimensions | Mounting dimensions | ||||
| Amax | Bmax | Cmax | Dmax | Emax | Fmax | |
| YCC19-25 | 176 | 45.5 | 122 | 74.5 | 35 | 50/60 |
| YCC19-32 | 180 | 56.5 | 132 | 83 | 40 | 50/60 |
| YCC19-43 | 180 | 56.5 | 132 | 83 | 40 | 50/60 |
| YCC19-63 | 190 | 74.5 | 154 | 127.5 | 59 | 100/110 |
| YCC19-95 | 190 | 85.5 | 160 | 127.5 | 67 | 100/110 |
| YCC19-115 | 190 | 85.5 | 160 | 127.5 | 67 | 100/110 |