YCM8N Series MCCB | CNC Electric
YCM8N Series MCCB
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

YCM8N Series MCCB
Picture
  • YCM8N Series MCCB
  • YCM8N Series MCCB

YCM8N Series MCCB

YCM8N Series circuit breakers are developed according to domestic and international market demand, as well as similar products.

Its rated insulation voltage is up to 1000V, suitable for AC 50-60Hz distribution network circuit whose rated operation voltage is up to 690V, rated operation current from 10A to 630A. It can distribute power, protect the circuit and power supply devices from the damage of overload,short circuit and under voltage, etc.

This series of circuit breaker is featured as high breaking capacity and short arcing. It can be installed vertically (namely vertical installation) and also installed horizontally (namely horizontal installation).

Standards: IEC60947-2.

Contact Us

Product Details

 

Operating conditions

1. Altitude: Below 2000m

2. Temperature: The temperature of media is not higher than 40°C ( +45°C for marine products) and not lower than -5°C.

3. Can withstand the bad environment of damp air, mold, radiation.

4. The maximum inclination is 22.5 degree.

5. Can work reliably under normal vibration of ship.

6. Can work reliably under earthquake(4g).

7. Should be no rain and snow hit.

8. The media should be no explosion danger and no gas which can corrode the metal or destroy the insulating or conductive dust.

Type designation

Type Frame Inm Breaking capacity Icu/lcs(kA) Operation Poles
YCM8N 125  S P
MCCB 125,250,400,630 125  15/10
250 25/18
400 35/25
630 35/25
  Default—handle direct operation;
  P—electric operation
  Z—rotating handle operation
3:three poles

 

Tripping mode and inner accessory Application Rated current(A)
300  125A
The first number indicate release mode
2: only with the instantaneous release device
3: complex release
Note: the last two numbers are attachment code
(see attachment table)
1: for distribution
2: for protecting the motor
125  10,16,20,32,40,50,63,80,100,125
250  100,125,140,160,180,200,225,250
400  250,300,315,350,400
630  400,500,630

Product Accessories

Accessory Product List

• Electrical Accessories: Shunt Trip, Undervoltage Release, Auxiliary Contact, Alarm Cotact,Integrated Auxiliary & Alarm Contact

• Mechanical Accessories: Phase Spacer, Extension Terminal, Manual Operating Mechnism, Electrical Operating Mechanism

• Installation Accessories: Fixed Plate Rear Accessory, Plug-in Accessory

Overview

YCM6 MCCB  Parts drawing

Inner accessories

Accessories of YCM8, YCM8LE, YCM8T/A, YCM8RT, YCM8E are the same.

YCM8N Series MCCB Accessories

Technical data

Frame Current(A) 125  250  400  630 
Type YCM8N-125S YCM8N-250S YCM8N-400S YCM8N-630S
Number of poles
Products  YCM8N-125S  YCM8N-250S  YCM8N-400S  YCM8N-630S
Rated current In(A) 10,16,20,25,32,40,
50,
63,80,100,125
100,125,140,160,180,
200,225,250
250,315,350,400 400,500,630
Rated voltage Ue(V) AC220/230V,400V,690V AC220/230V,400V,690V AC220/230V,400V,690V AC220/230V,400V,690V
Rated insulation voltage Ui(V) AC1000V AC1000V AC1000V AC1000V
Short Circuit
Breaking Capacity
(kA)Icu/lcs
AC220V 18/12 35/25 50/35 50/35
AC400V 15/10 25/18 35/25 35/25
AC690V 4/3 6/4 8/6 8/6
Operating Circle
Times
ON 600  3000  2000  2000 
OFF 900  7000  4000  4000 
Dimension(mm) 3P 75-130-66-84 106-165-78-101 150-257-112-150 150-257-112-150

a-b-c-ca

YCM8N-1

Electric operating device(MD)
External drive handle
Automatic release Thermal electromagnetic
type
Thermal electromagnetic
type
Thermal electromagnetic
type
Thermal electromagnetic
type

 

Technical Parameters

The thermal trip unit of the circuit breaker features an inverse time-delay characteristic;The magnetic trip characteristics are shown in Table 2 (for distribution use)

Table 2 Tripping Characteristics of Thermal-Magnetic and Magnetic

Trip Units

Rated Tripping
Current(A)
Thermal-magnetic trip unit(ambient temperature +40°℃) Operating current of the
magnetic trip unit(A)
1.05In(cold state)
Non-operating time (h)
1.30ln(hot state)
operating time (h)
10≤In≤63 6ln±20%,8ln±20%10ln
±20%,7In±20%
63<In≤630
Note:The non-operating time of the motor protection cirrcuit breaker is 2h at 1.0ln;the operating current is 1.20ln(hot state),and the operating
time is 2h.The operating current of the electromagnetic release is 12In±20%.

 

Curve

YCM8N Series MCCB Curve

Altitude Derating

When the altitude is below 2000m, it will not affect the performance of the circuit breaker. When exceeding this altitude, the decrease in air insulation characteristics and cooling capacity must be considered; the following correction factors are used for installations at altitudes exceeding 2000m:

Altitude(m) 2000  2500  3000  3500  4000  4500  5000 
Insulation Voltage Ui(V) 800  728  728  664  664  616  616 
Impulse Withstand Voltage Uimp(kV) 6.5  6.5 
Maximum Working Voltage Ue(V) 690  690  690  660  660  600  550 
Thermal Rating In(A)at 40℃Ambient Temperature 1.0ln 0.98ln 0.94In 0.92In 0.88ln 0.86ln 0.85In
Note:In high-altitude environments,the breaking capacity needs to be derated according to the corresponding rated working voltage,generally
selected between 75%and 50%,which is inversely proportional to the altiude.For details,please communicate with the technical department

Temperature Influence Characteristics

Influence of High Temperature on Release Performance (High Temperature Derating Characteristics)

When the temperature exceeds 40°C, the overload protection will have slight changes. In the release time/current curve, the Ir setting value of the circuit breaker must be corrected according to the following coefficients I/Ir.

Model Ambient Temperature(℃)
40  45  50  55  60 
YCM8N-125 0.96  0.89  0.83  0.75 
YCM8N-250 0.92  0.85  0.79  0.71 
YCM8N-400/630 0.94  0.87  0.81  0.73 

 Mechanical Accessories

YCM8N Series MCCB Accessories-1
YCM8N Series MCCB Accessories-2
YCM8N Series MCCB Accessories-3
Phase Spacers
·Phase spacers can enhance the  insulation  performance  between  phase conductors and
    can be installed from the front slot even after the switch is installed.
·Phase spacers are standard equipment,with 4  pieces for a 3P circuit  breaker.
Extension Terminals
Extension terminals are connected to the standard terminals of the circuit breaker to pro vide various wiring solutions in a small space:
• Straight extension terminals
• Pole pitch extension terminals
Busbars and extension terminals can be connected to the inlet or outlet end of the circuit
breaker.
Handle Operating Mechanism
·The  circuit  breaker  is  operated  by  rotating  the  handle.The  ergonomically  designed  ro-
   tating handle makes the operation of the circuit breaker more flexible.
·There  are two forms  of  rotating  handle  operating  mechanisms:
Direct rotating handle (round hand operation,square hand operation)
Extended rotating handle (round extended hand operation,square extended hand oper-
ation)
·User   visual    information/settings:
Three   position   indications:OFF,ON,TRIP
The circuit breaker cannot be closed when the door is open.
The door cannot be opened when closed.
The shaft length of the extended handle can be customized according to the distance
from the back of the circuit breaker to the door.
·Hand  operation  installation  diagram,accessory  installation  diagram
YCM8N Series MCCB Accessories-4
Hand operation external dimensions
YCM8N Series MCCB Accessories-5
 
 

CD2 Electric Operator

Electrical Characteristics and Wiring Diagram
 
YCM8N Series MCCB CD2

Note: The micro switch connected in series with the coil inside the K-shunt trip is a normally closed contact, which will disconnect automatically after the circuit breaker is tripped and close when closed.

P1 and P2 are external power inputs. SB1 and SB2 are operation buttons (provided by the user).

YCM8N Series MCCB CD2-1
Model A B H H1 a b
YCM8N-125 101  73  79  15  25  112 
YCM8N-250 118  92  79  17.5  35  142.4 
YCM8N-400/630 176  130  117  35.5  44  194 

Electrical Accessories

 YCM8N Series MCCB Electrical Accessories
YCM8N Series MCCB Electrical Accessories-1
 YCM8N Series MCCB Electrical Accessories-2

Overall and mounting dimensions(mm)

YCM8N Series MCCB Overall

Type Overall size(mm)
W L H A B W1 L1 L2 H1 H2 D D1
YCM8N-125 75  130  84  112  25  26  117  75  56  66  φ4 M6
YCM8N-250 106  165  101  126  35  35  147  97  69  78  φ5 M8
YCM8N-400/630 150  257  150  194  44  48  224  156  102  112  φ14 M10

Leave Your Message

Write your message here and send it to us

Related Products